Strany 1 - SHELF MANAGEMENT SOFTWARE

ReferenceSHELF MANAGEMENT SOFTWARESOFTWARE VERSION 4.2.xApril 2012 007-03261-0008

Strany 2 - Revision history

1Chapter10Shelf Management OverviewTheShelfManagerisresponsibleformonitoringconditionsofmodulesandothershelfcomponentsandcontrollingth

Strany 3 - Table of Contents

6Troubleshooting100General troubleshooting proceduresThissectionexplainshowtoacknowledgeandviewalarms,viewsystemevents,andchecksensoran

Strany 4

6Troubleshooting101Viewing the system event logYoucanviewamodule’slocalSELortheshelf’sSELusingtheopen‐sourceipmitoolutilityorthersys

Strany 5

6Troubleshooting102Investigating sensor valuesToviewthesensorvalueforasensorthathasgeneratedanalarm:1. WritedowntheFRUslotidentified

Strany 6 - What’s new in this manual

6Troubleshooting1032. ListthesensorsfortheSPMresource:qsb<resourceId>3. Notetheintaketemperatures.4. Repeatsteps1,2,and3fortheo

Strany 7 - Shelves and modules supported

6Troubleshooting104On the ATCA-6014 and ATCA-6016 shelves:Eachfantrayhasanexhausttemperaturesensor.Checktheexhausttemperaturesasfollows:1

Strany 8 - Related Radisys manuals

6Troubleshooting105IPMI frame structure and message flowTherearenoframesinIPMBmessages.Figure 10showsthemessageflowthroughanSCMpairfor

Strany 9 - Notational conventions

6Troubleshooting106OnlytheswitchingportionoftheSCMsactinActive‐Activemode.TheShMCsareneverindualactivestateunlessthere'sac

Strany 10 - Shelf Management Overview

6Troubleshooting107EachIPMCthatisnottheactiveShMCmonitorsits“ownside”ofthebus.Inotherwords,eachIPMCismonitoringitsownI2Cinter

Strany 11

6Troubleshooting108TheusercandotoseveralthingsrespondtoapersistentIPMBisolationissuewhenthereisashelfwideIPMBisolationalarmthat

Strany 12

6Troubleshooting109d. ToreturntheboardtoitsdefaultstatewhereitisjoinedonthatIPMByoucanagainusetheCLIasfollows:platform‐mgmt(fron

Strany 13

1Shelf Management Overview11Event and error managementTheShelfManagermanagesnormaleventsanderrorconditionsintheseways:•Powersdevicesupan

Strany 14

6Troubleshooting110Troubleshooting FRU and shelf operation issuesThissectionexplainshowtorespondtoFRUandshelfoperationalarmsandotherissu

Strany 15

6Troubleshooting111Responding to specific alarmsResponding to a communication lost alarmTheShelfManagerisnotgettingkeep‐aliveresponsesfromthe

Strany 16

6Troubleshooting112TherearenohardwarepresencedetectlinesinATCAbackplanes.TheShMSthusreliesonmessagebasedpings toperiodicallyquery

Strany 17

6Troubleshooting113Aftermakinganyshmgr.conffileupdate,remembertosynchronizeittothestandbySCMfromtheplatform‐managementCLIbeforerebo

Strany 18 - Software Architecture

6Troubleshooting114Responding to an IPMB isolated alarmThemodule’sIPMChasdetectedaproblemononeorbothofitsIPMBinterfaces,andhasisolate

Strany 19

6Troubleshooting1155. Disableeventgenera tiononthatsensorwiththesecommands:8<resourceId><sensorId>Thescreendisplaysthefinalme

Strany 20

6Troubleshooting1165. Lookforthe“inetaddr”value.TheSCMinthelower‐numberedslotinthechassisshouldhaveaneth1IPaddressof10.0.1.1.Th

Strany 21

6Troubleshooting117Beforeaddressingthepossiblecauseandtryingtocorrectit,someoftheinformationfromtheINSERTION_PENDINGstatemaybeusef

Strany 22

6Troubleshooting1183. IftheFRUisfoundtobeinM2andAutoInsertiontimerisnot‐1oralargevalue,checkthe stateofthe'FRUActivation

Strany 23

6Troubleshooting119c. Checkthe'DesiredPower'controlsonallFRUsinstalledonthatslot(parentandmanagedFRUs)andcheckifthetotal

Strany 24

1Shelf Management Overview12Shelf Manager complianceAsofthismanual’spublicationdate,theRadisysShelfManagerisfullycompliantwiththePICMG

Strany 25

6Troubleshooting120Responding to a fan not running1. CheckthattheShelfManagercancommunicatewiththefanandthatitisintheactivestate.Use

Strany 26

6Troubleshooting121Troubleshooting Shelf Manager issuesGeneral issuesWhenyouencounterproblemsrelatedtoshelfmanagement,checkthefollowingitem

Strany 27

6Troubleshooting122Make sure the Shelf Manager software is runningMakesuretheShelfManagersoftwareisrunning.TheActiveLEDoftheSCM(oroneS

Strany 28

6Troubleshooting123Blade and platform management issuesThetopicsinthissectionincludeShMC‐to‐IPMCcommunications,SELlocation,sensoreventrepo

Strany 29

6Troubleshooting124TypicallyeachIPMChasonlyitsowneventsinitsSEL.TheShMCsareexceptionstothisrulebecausetheylogeventsfromallIPMC

Strany 30

6Troubleshooting125Inventory Data Record (IDR) topicsRadisyscanprovideatoolcalledfruupdatethatcanbeusedtoupda teexistingFRUinventoryda

Strany 31

6Troubleshooting126Specific issuesTable 15listsspecificissuesthatcanbeencounteredwhileusingtheshelfmanagementandHPIservicesontheShel

Strany 32

6Troubleshooting127(continued from previous page)If the modules are still in debug mode, use these steps:• From each Shelf Manager module, verify that

Strany 33

6Troubleshooting128SCM resets abruptly forcing the LMP to reboot. There are no associated hot-swap events. Possible causes and steps to take are as fo

Strany 34

6Troubleshooting129Sessions cannot be opened on the HPI server. Error code: SA_ERR_HPI_OUT_OF_SPACEThe HPI server has reached the limit (32) for the n

Strany 35

1Shelf Management Overview13Figure 3. Shelf management component distribution in larger Radisys shelvesCarrier moduleProxy FRUIPMCOther FRUPEMIPMCIPMB

Strany 36

6Troubleshooting130RPT is incomplete; not all FRUs present in the shelf have associated Resources.1. Initiate a discovery operation using the CLI comm

Strany 37 - Disabling the Shelf Manager

6Troubleshooting131Resolving shelf FRU information issuesThissectionprovidesinformationonresolvingshelfFRUinformationproblems,includinghow

Strany 38 - Configuring multiple modules

6Troubleshooting132Restoring shelf FRU informationTheprocedurebelowisusefulwhentheshelfFRUinformationisbadandneedstobereplacedinthe

Strany 39

6Troubleshooting133Restoring shelf FRU information on ATCA-6002 shelvesTheATCA‐6002shelfusesafiletostoreshelfFRUinformation,becausetherei

Strany 40

6Troubleshooting134IPMB addresses of slots and FRUsTable 16showstheIPMBaddressesofslotsintheATCA‐6002shelf.Table 17showstheIPMBaddresse

Strany 41

6Troubleshooting135Resource types of slots and FRUs in the RPTTheresourcepresencetableidentifiesthetypeofeachresourceinthe2ndbyteofthe

Strany 42

6Troubleshooting136Thefollowingaretheslotresourcetypesinhex:F0 UnknownslotF1 SPMorRCMslotF2 ShelfdisplaypanelslotF3 VirtualSPMorvirt

Strany 43

AAppendix137Shelf Manager InitializationShelf Manager and HPI interface initializationTheshelfmanagementserver(ShMS)isinstalledaspartofthel

Strany 44 - Configuring RMCP

AShelf Manager Initialization138d. PopulatestheRPTwithresourcesandtheirassociatedresourcedatarecords(RDRs).Resourcesarecreatedforeach

Strany 45 - Setting the minimum fan speed

AShelf Manager Initialization139HPI subagent initializationWhentheHPIsubagentisstarted,initiallyyouwillseejustthestaticscalarobjectsdef

Strany 46 - Configuring HPI behavior

1Shelf Management Overview14Major elements of the shelf management infrastructureThefollowingsectionsdescribethemajorelementsoftheshelfmanag

Strany 47 - Configuring HPI multitasking

BAppendix140Shelf Management FilesThisappendixdescribesfilesintheshelfmanagementinfrastructure,includingprograms,scripts,andconfiguration

Strany 48

BShelf Management Files141Shelf Manager log fileTheShelfManagerlogfileis/tmp/shmgr/shmgr.log.Backupfilesinthesamedirectoryarecrea tedas

Strany 49 - Setting IDRs to read-only

CAppendix142IPMI Commands and Managed SensorsSupported IPMI commandsTheShelfManagersupportsallIPMIcommandslistedintheAdvancedTCABaseSpecif

Strany 50

CIPMI Commands and Managed Sensors143Table 18. Managed sensors for the Shelf Manager# Name Type CategoryNormal reading or event stateExplanation of

Strany 51

CIPMI Commands and Managed Sensors144Table 19. Managed sensors for each FRU# Name Type CategoryNormal reading or event stateExplanation of values256(0

Strany 52 - Configuring log settings

CIPMI Commands and Managed Sensors14530 Get Address Info failed31 Self Test Error32 Self Test Check failed33 Set IPMB-<A|B> State <Enable|Dis

Strany 53

CIPMI Commands and Managed Sensors146258(0x102)FRU Thermal StatusTemperature Threshold 0x1 State 0x1: Lower minor.State 0x2: Lower major.State 0x4: L

Strany 54

1Shelf Management Overview15Field replaceable units (FRUs)AdvancedTCAdefinestwotypesofFRUsthatarevisibletoandcontrolledthroughtheIPMIin

Strany 55

1Shelf Management Overview16Management controllers (IPMCs and MMCs)EachintelligentFRUincludesamanagementcontroller,eitheranIntelligentPlatfo

Strany 56 - ATCA‐2xxx#

1Shelf Management Overview17Theshelfcontainsanon‐volatilestoragedevicethatstoresshelfFRUinformation,includingdetailsoftheshelfitself

Strany 57 - Writing HPI applications

2Chapter18Software ArchitectureShelf management architectureShelfmanagementservicesfortheRadisysplatformarepartitionedacrosstwoprocessors:

Strany 58 - XX.XX.XX.XX

2Software Architecture19Shelf interfaceAttheshelfinterfacelevel,theShMCfirmwarerunsontheIPMC,performingthelow‐levelshelfmanagementope

Strany 59 - Using OpenHPI tools

Revision historyVersion Date Description-0000 December 2006 First edition.-0001 September 2007 Second edition. New features and editorial corrections

Strany 60 - Using SNMP

2Software Architecture20HPI architectureTheprimarymanagementinterfacetotheRadisysshelfmanagementservicesistheHardwarePlatformInterface(

Strany 61 - Enabling the HPI subagent

2Software Architecture21AsshowninFigure 5,theHPIclientlibrary(HCL)isadynamicallylinkedlibrary(DLL)thatprovidestheHPIAPIaswellas

Strany 62

2Software Architecture22RMCP,arequest‐responseprotocol,isasimplepacket‐basedcommunicationmechanism.RMCPpack etsincludeafieldthatindica

Strany 63

2Software Architecture23Forinformationonviewingthelogmessages,seeViewingthesystemeventlogonpage 101.Eventsmaybeclearedfromtheshel

Strany 64 - Running hpiapp

2Software Architecture24Basic and enhanced shelf management operationTheShelfManagerinanATCA‐6002shelfcanoperateintwomodes:enhancedandba

Strany 65 - Changing the shelf address

2Software Architecture25Inenhancedmode,theShelfManagerusesthe/etc/shmgr.conffile.TheShelfManagerdoesnotneedtousetheshmgr_basic.conf

Strany 66

2Software Architecture26Figure 7. SCM Shelf Manager redundancy Shelf Manager failover ComponentfailuresintheShMSandShMCaredetectedthroughthe

Strany 67

2Software Architecture27Peer communication loss causes failoverIfcommunicationbetweenthepeerShMCsbreaksdown,thefirstofthepreviouscommunic

Strany 68 - using the CLI

2Software Architecture28•UsingthefrontpanelresetbuttontoresettheactiveSCMeithermanuallyorusingHPIwiththesaHPIResourceResetStateSet()

Strany 69

2Software Architecture29Shelf FRU information redundancyDuringnormalshelfoperationwithredundantShelfManagers,therearealwaysatleastthreep

Strany 70 - Error conditions

3Table of ContentsPreface ...

Strany 71

2Software Architecture30Shelf FRU invalid alarmThisalarmsignalsacatastrophicfaultcondition.TheactiveShelfManagerkeepsallothermodulesin

Strany 72 - HPI FRU activation control

2Software Architecture31HPI server redundancyTheRadisy sHPIserverusesaredundancymodelverysimilartotheactive‐standbymodelusedbytheShel

Strany 73

2Software Architecture32InadditiontotheHPIdata,automaticoperationsaresynchronizedwiththepeerHPIserverstokeepHPIdatabasesinsync.Th

Strany 74

2Software Architecture33Shelf coolingToensurethatallmodulesintheshelfoperateefficiently,theiroperationaltemperaturesmustbemaintainedat

Strany 75

2Software Architecture34IfbothSCMsareremovedfromtheATCA‐6014orATCA‐6016shelf,theactiveRCMadjuststhefanstofullspeeduntiltheShelf

Strany 76

2Software Architecture35Shelf Manager cooling overrideTheShelfManagerprovidesautonomouscoolingmanagementfortheshelf.However,theremaybesi

Strany 77 - HPI parameter control

3Chapter36Configuring Shelf Manager and HPI BehaviorThischapterexplainshowto:• DisableorenabletheRadisysShelfManager.• Changetheoperating

Strany 78

3Configuring Shelf Manager and HPI Behavior37Disabling the Shelf ManagerImportant:WhenthereisonlyoneSCMorShelfManagermoduleintheshelf,di

Strany 79

3Configuring Shelf Manager and HPI Behavior38Enabling the Shelf ManagerImportant:Ifyouareremovingamodulefromanon‐RadisysorRadisysMPCH0001

Strany 80 - Example:

3Configuring Shelf Manager and HPI Behavior39Changing the Shelf Manager operating modeTheShelfManagerinanATCA‐6002shelfcanoperateintwomodes

Strany 81

4Table of ContentsChapter 4: Changing Shelf Settings Using HPI ... 53Radisys

Strany 82 - Managing Alarms and Events

3Configuring Shelf Manager and HPI Behavior40Overview of Shelf Manager and HPI configurationShelfManagerandHPIconfigurationsettingscanbeeither

Strany 83

3Configuring Shelf Manager and HPI Behavior41Table 4. Shelf Manager and HPI configuration settingsShelf Manager configuration settings Parameter to ed

Strany 84

3Configuring Shelf Manager and HPI Behavior42Editing the shmgr.conf configuration file File‐basedconfigurationsettingsarestoredinthe/etc/shmgr.

Strany 85

3Configuring Shelf Manager and HPI Behavior43Configuring Shelf Manager behaviorThissectiondescribestheshelfmanagementconfigurationsettingsyou

Strany 86

3Configuring Shelf Manager and HPI Behavior44Disabling the HPI serviceTheSHMS_CMDLINE_ARGSparameterin/etc/shmgr.confletsyoudisableHPIservice.

Strany 87

3Configuring Shelf Manager and HPI Behavior45Configuring the system event log (SEL)TheSHMS_SYNC_SEL_TIMEparameterin/etc/shmgr.confsetsthe syste

Strany 88

3Configuring Shelf Manager and HPI Behavior46Configuring HPI behaviorThissectiondescribestheHPIconfigurationsettingsyoucanchangebyeditingH

Strany 89

3Configuring Shelf Manager and HPI Behavior47• HSD_CHASSIS_FRU_MONITOR_ENABLEenablesthemonitoringofshelfFRUs,includingthealarmmoduleandfan

Strany 90

3Configuring Shelf Manager and HPI Behavior48Assigning an entity type for a new FRUTheHSD_FRU_ENTITY_TYPEparameterin/etc/shmgr.confletsyouassig

Strany 91

3Configuring Shelf Manager and HPI Behavior49Loading saved HPI resource configuration filesTheHSD_LOAD_SAVED_CONFIGURATIONparameterin/etc/shmgr.co

Strany 92

5Table of ContentsAppendix A: Shelf Manager Initialization... 137She

Strany 93

3Configuring Shelf Manager and HPI Behavior50Configuring the Shelf Manager in basic modeForaShelfManagerrunningontheATCA‐6002shelf,aconfigur

Strany 94

3Configuring Shelf Manager and HPI Behavior51Editing the rsyshsd.conf configuration fileForeachfrontmodulethereareblade HPIconfigurationsetti

Strany 95

3Configuring Shelf Manager and HPI Behavior52Configuring log settings•TheRSYSHSD_LOG_FILEparameteriswhereyoucanspecifythenameofthelogfile

Strany 96

4Chapter53Changing Shelf Settings Using HPIThischapterdescribestheRadisysHPIimplementation,includinghowHPIaffectsyourapplications,howto

Strany 97

4Changing Shelf Settings Using HPI54TheDomainIdneededforopeningHPIsessionsontheRadisysplatform’sHPIInterfaceisderivedfromtheShelfMan

Strany 98

4Changing Shelf Settings Using HPI55ThefollowingistheResourceIdformatusedbyshelfandShelfManagerresourcesintheHPIresourcepresencetabl

Strany 99

4Changing Shelf Settings Using HPI56Using the platform-management CLIYoucanaccessseveralcommandmodes,includingplatform‐managementmode,fromth

Strany 100 - Troubleshooting

4Changing Shelf Settings Using HPI57Writing HPI applicationsThefollowingarerequiredtocreateanHPIapplication:SaHpi.h TheofficialHPIB.03.02h

Strany 101

4Changing Shelf Settings Using HPI58TorunanyHPIapplicationthatlinkswiththeRadisysHPIclientlibrary,libhcl.so,considerthefollowing:•The

Strany 102

4Changing Shelf Settings Using HPI59Using OpenHPI toolsOpenHPIisanopensourceprojectcreate dwiththeintentofprovidinganimplementationofSA

Strany 103

6PrefaceAbout this manualThismanualdescribestheRadisysShelfManagementSoftware(the“ShelfManager”),theHardwarePlatformInterface(HPI)serv

Strany 104

4Changing Shelf Settings Using HPI60Using SNMPSNMPaccesstotheshelfmanagementfunctionalityisprovidedthroughtheHPI‐B0101‐MIBmodule,whichwo

Strany 105

4Changing Shelf Settings Using HPI61Eachofthesetablesisindexedby:saHpiDomainId,saHpiResourceIdsaHpiResourceIsHistoricalsaHpiCtrl*EntryIdobject

Strany 106

4Changing Shelf Settings Using HPI62Configuring HPI subagent loggingHPIsubagentloggingisdisabledbydefault.Toenablelogging:1. Inthe/etc/rc.d

Strany 107

4Changing Shelf Settings Using HPI63Using the example HPI application (hpiapp)RadisysprovidesanexampleHPIapplication,hpiapp,thatiscompliantw

Strany 108

4Changing Shelf Settings Using HPI64Running hpiappThefollowingexamplesshowhowtorunthehpiappexampleapplicationtoconnecttoanHPIserverru

Strany 109

4Changing Shelf Settings Using HPI65Changing the shelf address Thefirst4bytesoftheshelfaddressshouldbechangedmanuallytouniquelyidentify

Strany 110

4Changing Shelf Settings Using HPI66Changing the Shelf Manager IP address TheactiveshelfmanagementserverhasadedicatedIPaddressthatisderive

Strany 111

4Changing Shelf Settings Using HPI67YoucaneitherchangeonelineatatimeorchangeallthreelinestogetherusingthesaHpiControlSet()function.

Strany 112

4Changing Shelf Settings Using HPI68Changing the FRU power-on sequence using the CLIYoucanusetheCLIto:•Viewthecurrentpower‐onsequence• Chang

Strany 113

4Changing Shelf Settings Using HPI69FRU power-on sequence controlsTheshelfresource(ResourceId0x01)providesasetofHPIdiscretecontrols,eacho

Strany 114

Preface7Shelves and modules supportedTheShelfManagerdescribedinthismanualisavailableontheseRadisysshelveswithasupportedfrontmodulein

Strany 115

4Changing Shelf Settings Using HPI70FRU power-on sequence commit status sensorTheshelfresourcecontainsanadditionalsensorcalledtheFRUpower‐on

Strany 116

4Changing Shelf Settings Using HPI71Querying the current hot-swap state of a FRUYoucanqueryaFRU’scurrenthot‐swapstate:•UsingtheCLIcommandst

Strany 117

4Changing Shelf Settings Using HPI72Overriding the default ShMS hot-swap mechanism WhetheraFRUsittinginaparticularslotisactivatedbytheShel

Strany 118

4Changing Shelf Settings Using HPI73Whileinmanualmode,youcanalsoupdatetheDelayBeforeNextPowerOnforthathardwareaddress.Thisisthean

Strany 119

4Changing Shelf Settings Using HPI74Overriding the cooling algorithmSystemmanagerscancompletelyoverridetheShelfManager’scoolingalgorithmand

Strany 120

4Changing Shelf Settings Using HPI75Overriding the cooling algorithm with an HPI applicationThefollowingstepsillustratehowyoucandothisusingH

Strany 121

4Changing Shelf Settings Using HPI76Changing shelf power propertiesTheshelfresourcecontainstwocontrolsthatenablesystemmanagerstoupdateshel

Strany 122

4Changing Shelf Settings Using HPI77HPI parameter controlTheshelfresources,alongwithallintelligentFRUresourcesandslotresources,supportthe

Strany 123

4Changing Shelf Settings Using HPI78HPI server parameter control configuration files Eachresourcehastwoconfigurationfiles:onefordefaultsettin

Strany 124

4Changing Shelf Settings Using HPI79How configuration files are created for a new resourceDuringHPIinitialization(whenresourcesarebeingcreated

Strany 125

Preface8Where to get more product informationVisittheRadisyswebsiteatwww.radisys.comforproductinformationandotherresources.Downloads(man

Strany 126

4Changing Shelf Settings Using HPI80Saving a configuration file to store custom settings for a resourceAfteraresourcehasbeenconfiguredtoadesir

Strany 127

4Changing Shelf Settings Using HPI81Error conditions TheparametercontroloperationsSAHPI_DEF A ULT_PARMorSAHPI_RESTORE_PARMwillfailandreturn

Strany 128

5Chapter82Managing Alarms and EventsThischapterdescribes:•TheShelfManager’sroleinmanagingalarms.•Howyoucanchangethealarmreportingbyass

Strany 129

5Managing Alarms and Events83Domain alarm types and troubleshooting overviewTable 8liststhealarmandsensortypesalongwithsampledescriptionsan

Strany 130

5Managing Alarms and Events84Threshold alarmsThefirsteightalarmtypesinTable 8arethresholdalarmswhichindicatethatathresholdsensordetect

Strany 131

5Managing Alarms and Events85UpperMajortemperatureeventsma yindicatethattheambienttemperatureistoohigh,inwhichca seyoumightneedtol

Strany 132

5Managing Alarms and Events86Resource utilization alarmsTheresourceutilizationalarmsindicatethattheShelfManagerisusingahighpercentageof

Strany 133

5Managing Alarms and Events87Domain alarm table entriesThealarmstringsarebasedontheassociatedsensorevents.Textwithinthealarmstringindic

Strany 134

5Managing Alarms and Events88Collecting information for the alarm configuration fileForeachtypeofFRUandeachsensorforwhichyouwill assignse

Strany 135

5Managing Alarms and Events89Table 11liststheinformationneededtoidentifythesensor,theeventstate,andthenewseveritytoassign.Table 11.

Strany 136

Preface9IPMIIntelligentPlatformManagementInterfaceSpecificationSecondGeneration,v2.0,DocumentRevision1.0,Intel,Hewlett‐Packard,NEC,Dell

Strany 137 - Shelf Manager Initialization

5Managing Alarms and Events90Configuration file structure and contentsThe/etc/shmgralarm.conffileusesthisstructureforitscontents:FRUidentific

Strany 138

5Managing Alarms and Events91Alarm configuration procedureChangestothealarmconfigurationfiletakeeffectwhentheShelfManagerisrestarted.Thi

Strany 139

5Managing Alarms and Events92ATCA-6000 shelf display and alarm indicatorsTheshelfdisplaypanel(SDP)ontheATCA‐6000shelfconsistsofthefollowin

Strany 140 - Shelf Management Files

5Managing Alarms and Events93Figure 9. Format of alarm messages on the SDPSet to the location of the resource that has the alarm. The format is NNM fo

Strany 141

5Managing Alarms and Events94ATCA-6006 shelf alarm indicatorsTheoptionalshelfalarmpanelontheATCA‐6006shelfconsistsofthefollowing:•ShelfPo

Strany 142

5Managing Alarms and Events95ATCA-6014 and ATCA-6016 shelf alarm indicatorsTheATCA‐6014andtheATCA‐6016shelvesbothhaveashelfalarmpanel(SAP)

Strany 143

5Managing Alarms and Events96Thecontrolsforthetelcoalarmcontacts(AlarmCritical,AlarmMajor,andAlarmMinor)arestandardHPIcontrols.Onth

Strany 144

5Managing Alarms and Events97Parameter values for setting alarm controlsThefollowinglistidentifiesthepossiblesaHpiControlSet()functionparamete

Strany 145

6Chapter98TroubleshootingThischapterprovidesdetailedinformationonthefollowingissues:•AvailablediagnostictoolsforFRUandShelfManagerprob

Strany 146

6Troubleshooting99Using the Shelf Manager diagnostics utilityTheshmgrdiagutilitygathersinformationonthecurrentstateoftheShelfManager,the